Fire Water Storage Tank Sizing

Dedicated fire-water reserve from sprinkler, hydrant and hose demands with explicit duration, reserve and usable-volume checks.

Free · no sign-in required

Purpose

Establish the dedicated fire-water reserve a building must hold, so the tank, its compartments and the pump house can be sized and located at concept stage.

Inputs required

The systems installed and their design flows, the required duration for each, whether demands are assumed simultaneous or the largest single demand governs, the unusable volume below the pump suction, and any reserve or compartment requirement.

Standards followed

National Building Code of India 2016 Part 4, IS 15105:2021 for automatic sprinkler installations, IS 3844 for hydrant and hose-reel systems, IS 13039 for external hydrant systems, and NFPA 13, NFPA 14 and NFPA 22 for sprinklers, standpipes and private fire-service water tanks. Verify the edition adopted by the project or authority having jurisdiction.

Inputs

L/min
Enter the hydraulically calculated or code-prescribed demand
min
L/min
min
L/min
Use only when not already included in another demand
min
Use the combination required by the adopted code and AHJ
%
Suction clearance, low-level cut-off and dead storage
%
nos

Results

Gross fire-water storage
448.8 m³
224.4 m³ per compartment · 4180 L/min governing flow

Summary: The gross fire-water storage is 448.8 m³ (224.4 m³ per compartment · 4180 L/min governing flow). All engineering checks pass.

Demand volumes
Sprinkler reserve
114.0 m³
Hydrant / standpipe reserve
273.6 m³
Additional hose reserve
0.0 m³
Net usable reserve
387.6 m³
Tank selection
Combination basis
Simultaneous sum
Gross capacity
448.8 m³
Compartments
2 nos
Capacity per compartment
224.4 m³
Engineering checks
Positive duration provided for every active demand
Unusable allowance included — Confirm suction low-level, freeboard and dead storage with the tank arrangement
At least two compartments for maintainability — Verify compartmentation and usable reserve requirements with the AHJ
Demand combination explicitly selected

Step-by-step working

  1. 1. Design basis — Sprinkler design flow: 1900 L/min; Sprinkler duration: 60 min; Hydrant / standpipe flow: 2280 L/min; Hydrant / standpipe duration: 120 min; Additional hose-stream flow: 0 L/min; Hose-stream duration: 60 min; Demand combination: Simultaneous — add all demands; Unusable volume allowance: 5 %; Design reserve: 10 %; Tank compartments: 2 nos.
  2. 2. Apply formulae — Individual reserve = design flow × required duration ÷ 1000 · Net usable reserve = sum of simultaneous demand volumes, or largest non-simultaneous volume · Gross tank volume = net reserve × (1 + design reserve) ÷ usable fraction · Capacity per compartment = gross volume ÷ compartment count
  3. 3. Intermediate values — Sprinkler reserve = 114.0 m³; Hydrant / standpipe reserve = 273.6 m³; Additional hose reserve = 0.0 m³; Net usable reserve = 387.6 m³; Combination basis = Simultaneous sum; Gross capacity = 448.8 m³.
  4. 4. Final selection — Gross fire-water storage: 448.8 m³
Formulae used
  • Individual reserve = design flow × required duration ÷ 1000
  • Net usable reserve = sum of simultaneous demand volumes, or largest non-simultaneous volume
  • Gross tank volume = net reserve × (1 + design reserve) ÷ usable fraction
  • Capacity per compartment = gross volume ÷ compartment count
Assumptions & limits
  • The designer supplies code/AHJ-approved flow, duration and simultaneity; the calculator does not infer hazard classification.
  • Domestic/process storage is excluded unless the approving authority expressly permits a combined tank with a protected fire reserve.
  • The gross result includes the entered unusable allowance but not structural freeboard unless included by the user.
  • Confirm refill provisions, suction geometry, vortex protection, access and sectional operation during detailed design.
Standards: NBC 2016 Part 4 (fire-water supply by occupancy/building type) · IS 15105:2021 (sprinkler demand and water supply) · IS 3844 (internal hydrants) · IS 13039 (external hydrants) · NFPA 13 (sprinkler demand/duration) · NFPA 14 (standpipe demand) · NFPA 22 (water tanks); verify the edition adopted by the project/AHJ

Engineering reference & methodology

Volume follows flow and duration

The required volume is the governing design flow multiplied by the required duration. The flow comes from the system's design density and assumed operating area for sprinklers, or from the number of hydrants and hose reels assumed to operate simultaneously with their nozzle flow. The duration is set by the occupancy hazard classification and the code in force, not chosen by the designer.

Simultaneous versus largest single demand

Whether sprinkler and hydrant demands must be added or whether the largest alone governs is the decision that most changes the answer, often by a factor approaching two. Codes differ, and the authority having jurisdiction may impose the more onerous case. Resolve this in writing before the tank volume is fixed, because the tank and pump room footprint is set very early in the architectural layout and cannot be enlarged later without major rework.

Usable versus gross volume

Only water above the pump suction and vortex-inhibitor level is available to fight a fire. Water below that level, and any volume lost to the tank's dead bottom or to a sloping base, is unusable and must be added on top of the required reserve. Sizing on gross geometric capacity is a common and serious error: the system then runs out of water before the required duration has elapsed, precisely when the fire is at its most developed.

Dedicated reserve and compartmentation

The fire reserve must be dedicated. Domestic draw-off has to be arranged so it cannot deplete the fire volume, typically by taking the domestic suction at a higher level. Where the code requires it, the tank is divided into at least two compartments with independent inlets, outlets and isolation, so that one can be drained for cleaning or repair while the other keeps the system in service. A single undivided tank means the entire fire protection system is offline whenever the tank is maintained.

Replenishment and make-up

The inlet must be able to refill the tank within the period the code allows after a draw-down. A reserve that meets the volume requirement but refills slowly leaves the building unprotected for an extended time after an incident or a test. Confirm the available inlet pressure and flow from the source, and confirm that the level controls and low-level alarms are monitored.

Failure consequences and verification

An undersized or partly unusable reserve means the sprinklers or hydrants lose water mid-incident, the fire pump cavitates and the building's fire strategy fails at the point it is needed; it is also a common cause of refusal at occupancy certification. Before the result is used, verify the hazard classification and duration against the code edition the authority enforces, confirm the simultaneous-operation assumption with the authority in writing, check that the stated usable volume reflects the actual suction and vortex-inhibitor levels, and confirm the pump suction arrangement, compartmentation and make-up rate with the fire pump and tank designs.

Results are preliminary design guidance. Verify every value against the edition of each standard adopted by your project or authority having jurisdiction, and against manufacturer performance data, before using it in design or procurement.