Fire Water Storage Tank Sizing
Dedicated fire-water reserve from sprinkler, hydrant and hose demands with explicit duration, reserve and usable-volume checks.
Free · no sign-in requiredPurpose
Establish the dedicated fire-water reserve a building must hold, so the tank, its compartments and the pump house can be sized and located at concept stage.
Inputs required
The systems installed and their design flows, the required duration for each, whether demands are assumed simultaneous or the largest single demand governs, the unusable volume below the pump suction, and any reserve or compartment requirement.
Standards followed
National Building Code of India 2016 Part 4, IS 15105:2021 for automatic sprinkler installations, IS 3844 for hydrant and hose-reel systems, IS 13039 for external hydrant systems, and NFPA 13, NFPA 14 and NFPA 22 for sprinklers, standpipes and private fire-service water tanks. Verify the edition adopted by the project or authority having jurisdiction.
Inputs
Results
Summary: The gross fire-water storage is 448.8 m³ (224.4 m³ per compartment · 4180 L/min governing flow). All engineering checks pass.
- Sprinkler reserve
- 114.0 m³
- Hydrant / standpipe reserve
- 273.6 m³
- Additional hose reserve
- 0.0 m³
- Net usable reserve
- 387.6 m³
- Combination basis
- Simultaneous sum
- Gross capacity
- 448.8 m³
- Compartments
- 2 nos
- Capacity per compartment
- 224.4 m³
Step-by-step working
- 1. Design basis — Sprinkler design flow: 1900 L/min; Sprinkler duration: 60 min; Hydrant / standpipe flow: 2280 L/min; Hydrant / standpipe duration: 120 min; Additional hose-stream flow: 0 L/min; Hose-stream duration: 60 min; Demand combination: Simultaneous — add all demands; Unusable volume allowance: 5 %; Design reserve: 10 %; Tank compartments: 2 nos.
- 2. Apply formulae — Individual reserve = design flow × required duration ÷ 1000 · Net usable reserve = sum of simultaneous demand volumes, or largest non-simultaneous volume · Gross tank volume = net reserve × (1 + design reserve) ÷ usable fraction · Capacity per compartment = gross volume ÷ compartment count
- 3. Intermediate values — Sprinkler reserve = 114.0 m³; Hydrant / standpipe reserve = 273.6 m³; Additional hose reserve = 0.0 m³; Net usable reserve = 387.6 m³; Combination basis = Simultaneous sum; Gross capacity = 448.8 m³.
- 4. Final selection — Gross fire-water storage: 448.8 m³
- Individual reserve = design flow × required duration ÷ 1000
- Net usable reserve = sum of simultaneous demand volumes, or largest non-simultaneous volume
- Gross tank volume = net reserve × (1 + design reserve) ÷ usable fraction
- Capacity per compartment = gross volume ÷ compartment count
- The designer supplies code/AHJ-approved flow, duration and simultaneity; the calculator does not infer hazard classification.
- Domestic/process storage is excluded unless the approving authority expressly permits a combined tank with a protected fire reserve.
- The gross result includes the entered unusable allowance but not structural freeboard unless included by the user.
- Confirm refill provisions, suction geometry, vortex protection, access and sectional operation during detailed design.
Engineering reference & methodology
Volume follows flow and duration
The required volume is the governing design flow multiplied by the required duration. The flow comes from the system's design density and assumed operating area for sprinklers, or from the number of hydrants and hose reels assumed to operate simultaneously with their nozzle flow. The duration is set by the occupancy hazard classification and the code in force, not chosen by the designer.
Simultaneous versus largest single demand
Whether sprinkler and hydrant demands must be added or whether the largest alone governs is the decision that most changes the answer, often by a factor approaching two. Codes differ, and the authority having jurisdiction may impose the more onerous case. Resolve this in writing before the tank volume is fixed, because the tank and pump room footprint is set very early in the architectural layout and cannot be enlarged later without major rework.
Usable versus gross volume
Only water above the pump suction and vortex-inhibitor level is available to fight a fire. Water below that level, and any volume lost to the tank's dead bottom or to a sloping base, is unusable and must be added on top of the required reserve. Sizing on gross geometric capacity is a common and serious error: the system then runs out of water before the required duration has elapsed, precisely when the fire is at its most developed.
Dedicated reserve and compartmentation
The fire reserve must be dedicated. Domestic draw-off has to be arranged so it cannot deplete the fire volume, typically by taking the domestic suction at a higher level. Where the code requires it, the tank is divided into at least two compartments with independent inlets, outlets and isolation, so that one can be drained for cleaning or repair while the other keeps the system in service. A single undivided tank means the entire fire protection system is offline whenever the tank is maintained.
Replenishment and make-up
The inlet must be able to refill the tank within the period the code allows after a draw-down. A reserve that meets the volume requirement but refills slowly leaves the building unprotected for an extended time after an incident or a test. Confirm the available inlet pressure and flow from the source, and confirm that the level controls and low-level alarms are monitored.
Failure consequences and verification
An undersized or partly unusable reserve means the sprinklers or hydrants lose water mid-incident, the fire pump cavitates and the building's fire strategy fails at the point it is needed; it is also a common cause of refusal at occupancy certification. Before the result is used, verify the hazard classification and duration against the code edition the authority enforces, confirm the simultaneous-operation assumption with the authority in writing, check that the stated usable volume reflects the actual suction and vortex-inhibitor levels, and confirm the pump suction arrangement, compartmentation and make-up rate with the fire pump and tank designs.
Results are preliminary design guidance. Verify every value against the edition of each standard adopted by your project or authority having jurisdiction, and against manufacturer performance data, before using it in design or procurement.